Applications
As flame-retardant three or four conductor power cables rated 600 volts, 90 Deg. C. in wet or dry locations. Specifically approved for installation in cable trays per Article 336 of the NEC. Type TC cable is also approved for use in Class I and II, Division 2 hazardous locations. Cables may be installed in open air, in ducts or conduits, in tray or trough, or direct buried.
Construction
Class B stranded uncoated copper conductor, XLPE crosslinked polyethylene insulation, surface print phase identification. Three or four insulated conductors twisted with a Class B stranded uncoated copper grounding conductor and suitable fillers, cable tape, PVC jacket overall, surface printed.
Standards
1) Listed by UL as Type TC per Standard 1277 for Tray Cables.
2) Individual conductors UL listed as Type XHHW-2.
3) Overall jacket UL listed as Sunlight Resistant.
4) Cables pass UL and IEEE-383 ribbon burner flame tests.
5) Cables pass IEEE1202/CSA FT4 (70,000 BTU/hr) cable tray flame test (2 AWG and larger).
6) Cables UL listed for Direct Burial.
7) Cables UL listed for Open Wiring.
8) Cables meet requirements of ICEA S-9568/NEMA WC70.
Notes
AMPACITY in accordance with the National Electrical Code for cables in uncovered cable tray without maintained spacing and for cables in raceway or directly buried; at the conductor temperature indicated, in wet or dry locations, 30oC ambient temperature.
Grounding conductor per UL Standard 1277 for Type TC Tray Cable.
Options
Bare or Tinned Copper
Flexible stranded conductors
E1 or E2 color codes
EPR Insulation
CPE, CSPE, LSOH jackets
Overall copper tape shield
Overall copper braid shield
Overall longitudinal corrugated copper shield
Overall mylar tape shield with drain wire
1000 volt rated construction
Consult us for a variety of alternate constructions for specific applications.